Steel in fire — EN 1993-1-2
Fire resistance of carbon steel members to EN 1993-1-2 — the steel temperature at the required time, the resistances at that temperature, the critical temperature, and what is left to you.
Design checks 11 min read
The ec3.fire-resistance module verifies a carbon steel member in a nominal fire to
EN 1993-1-2:2005 with AC:2009, by the simple calculation models of §4.2. For the required
time you state, it works out:
- the steel temperature the member reaches, unprotected or behind fire protection;
- its resistances at that temperature, §4.2.3, against the forces of the fire situation;
- its critical temperature , and the time the member takes to reach it.
The module is in New check under EN 1993-1-2, and counts towards the plan's design checks per project. The second-generation revision of EN 1993-1-2 is not implemented; each result states the edition it used.
Scope
| Covered | Refused, with a message | |
|---|---|---|
| Material | Carbon steel | Stainless steel, which reads Annex C of EN 1993-1-2 |
| Sections | I and H with equal flanges, from a catalogue or the section editor, rolled or welded; boxes, rectangular and square hollow sections included | Channels, angles, tees, circular tubes, cold-formed sections, I sections with unequal flanges, sections drawn as an outline or built up from plates, and generic sections |
| Fire | The nominal fires of EN 1991-1-2 §3.2: standard (ISO 834), external, hydrocarbon | Parametric fires (EN 1991-1-2 Annex A) and external steelwork (EN 1993-1-2 Annex B) |
| Temperature | Uniform over the section and along the member | A temperature that varies over the section or the length, beyond the factors below |
What the check reads
On the check, once for all its members:
| Setting | Default | What it is |
|---|---|---|
| 60 min | The required fire resistance, R: the time the member must keep its load-bearing function, §2.1.2 | |
| Fire curve | Standard (ISO 834) | The nominal fire, with its convection coefficient : 25 W/m²K, 50 for hydrocarbon |
| 0.65 | The reduction factor of §2.4.2(2): see the actions in fire | |
| 1.0 | Partial factor in the fire situation, §2.3 | |
| 1.0 | For (4.3), (4.8) and (4.16), and the cap | |
| Class 4 | The route for a Class 4 section, §4.2.3.6: below | |
| 350 °C | The limit for a Class 4 section on that route, §4.2.3.6 NOTE 2 | |
| Protection | Contour | How a protected member is encased: a contour encasement follows the steel, a hollow one (boards) boxes it |
| , , | 0.12 W/mK, 350 kg/m³, 1200 J/kgK | The protection's thermal conductivity, density and specific heat |
is set by the project's national annex, as on the other steel checks. and stay at the recommended values whatever the annex, so set them on the check if your annex chooses others.
The protection values that come with the check are those of the sprayed product in the JRC's worked example EUR 26698, Example 1. While they are unchanged, the result says so. State your product's values, as its ENV 13381-4 assessment gives them: §3.4.3 leaves them to the product.
Per member, under Settings per member:
| Setting | Default | What it is |
|---|---|---|
| 0 mm | The protection's thickness. 0 is unprotected steel | |
| Sides exposed | 4 | Four, or three with a slab on the top flange. Sets the section factor and |
| 1.0 | §4.2.3.3(8): 0.85 at the supports of a statically indeterminate beam, 1.0 elsewhere. One value for the member | |
| Flange held all along | none | A flange a slab or sheeting holds laterally along the whole member: see lateral-torsional buckling |
| Cantilever root | Free to warp | What a cantilever's root does to warping, for . Read only on a member with a free end |
From the model: the section and its fabrication, the material's (reduced for thickness by EN 1993-1-1 Table 3.1, as the EN 1993-1-1 check reads it), the member's buckling factors , and , its lateral restraints, the height its load acts at, and the forces of the ULS design combinations the check reads.
The actions in fire
The forces of the fire situation are , §2.4.2(2), taken from the ULS design combinations the check reads. EN 1993-1-2 recommends , and 0.7 for imposed load of category E. If you work it out for your loads by (2.5), enter that value.
The accidental combination of EN 1990 (6.11b) is not generated. A combination at factor 1.0 marked ULS would also be read by every other ULS check, and pass them all, so the route is the only one.
Under each combination the check takes the peak of each force along the member, in compression and in tension, , and , and verifies them together, as if they met in one section. Where the peaks are at different places that is on the safe side.
The steel temperature
The steel is heated from 20 °C in steps of one second, with the gas temperature of the fire curve (EN 1991-1-2 (3.4) to (3.6)) at the middle of each step, the steel's specific heat of (3.2), = 7850 kg/m³, = 0.7, = 1 and configuration factor 1. The run goes on to the required time, and at least to four hours, so the time to the critical temperature can be read past .
| Unprotected, (4.25) | Protected, (4.27) | |
|---|---|---|
| Section factor | from the section's own perimeter, the root radii of an I included. Three sides leave the top flange's width out | : the perimeter for a contour encasement; for a hollow one, on three sides |
| Shadow effect | for an I, (4.26a); 1 for a box | — |
| Limits | not below 10 m⁻¹, §4.2.5.1(5) | while the gas heats |
The result reports the section factor the steel heated by, and whether the member is protected.
Resistances at the steel temperature
The section is classified by Table 5.2 of EN 1993-1-1 with , (4.2). Every resistance is at the uniform temperature , with , and interpolated in Table 3.1:
| Check | Clause | What the module does |
|---|---|---|
| Tension | 4.2.3.1, (4.3) | |
| Compression | 4.2.3.2, (4.5) | The lesser about and , with , (4.7), and the one fire curve , (4.6), with no plateau |
| Bending, Class 1 and 2 | 4.2.3.3, (4.10) | , over , capped at |
| Bending, Class 3 | 4.2.3.4, (4.17) | The same on |
| Lateral-torsional buckling | 4.2.3.3 (4.11), 4.2.3.4 (4.19) | from , with taken as , the NOTE's conservative choice |
| Shear | 4.2.3.3, (4.16) | along at |
| Compression with bending | 4.2.3.5, (4.21a) and (4.21b); (4.21c) and (4.21d) for Class 3 | , and with , and , and from the moment diagram by Figure 4.2. Bending about both axes with no axial force reads (4.21a) with : the linear sum |
| Tension with bending | EN 1993-1-1 §6.2.1(7), (6.2) | EN 1993-1-2 has no rule of its own, so the linear sum, on the resistances in fire |
is 1.0 on four sides, and on three sides 0.70 unprotected or 0.85 protected, §4.2.3.3(7). Where the shear exceeds half of , is reduced by EN 1993-1-1 (6.29) and (6.30), as (4.8) asks. is read in the form that ends in , the one the published worked beam-column reproduces.
Buckling lengths are those at 20 °C, §4.2.3.2(3): from the member's factors, 1 where none is stored. The shorter lengths §4.2.3.2(5) allows for a continuous column in a braced frame are not applied for you.
Lateral-torsional buckling
comes from at 20 °C, (4.15), on the member as it is held: the moment diagram, its lateral restraints, the height of its load, a cantilever's free end and root. It is read at any , because (4.11) to (4.15) print no plateau. It is read on I and H sections only: a box is not checked for lateral-torsional buckling in fire.
If Flange held all along names a flange, and the moment compresses that flange all along the member, the member is the restrained beam of (4.8) to (4.10), with no lateral-torsional buckling, and the result says so. Where the moment reverses and compresses the other flange, lateral-torsional buckling is read.
Class 4
| Class 4 | What happens |
|---|---|
| θ_crit (default) | §4.2.3.6: the member holds while . The utilisation is , and the result gives the time is reached |
| Annex E | and at 20 °C, and of Table E.1 in place of everywhere. A section whose effective section isn't derived here is refused, with the advice to use |
The critical temperature
is the temperature at which the governing utilisation reaches 1, solved on Table 3.1 between 20 and 1200 °C. The resistances only fall as the steel heats, so a utilisation below 1 at , a steel temperature below and a time to beyond say the same thing. Where neither compression nor lateral-torsional buckling acts, §4.2.4(2) allows (4.22), and its value on is printed beside the solved one. If already exceeds the resistance at 20 °C, the result says so and there is no critical temperature.
The module is held to eleven printed worked examples, from the JRC (EUR 27346 and EUR 26698) and from the SCI's articles in NSC, each recomputed from its printed inputs: columns, a restrained and an unrestrained beam, a Class 1 and a Class 4 beam-column, and both kinds of heating. One of them, through the whole module: JRC EUR 26698 Example 1, an IPE 360 secondary beam in S275 over 7 m, its top flange held by the slab, carrying 14.105 kN/m in the fire situation.
| Section factor | Result | ||
|---|---|---|---|
| Unprotected, four sides | = 0.705 × 186 m⁻¹ | 667 °C, reached at 17 min | Holds R15, fails R30 |
| Sprayed 10 mm, three sides | = 163 m⁻¹ | 687 °C | 631 °C at 60 min: holds R60 |
What the result shows
Each member's row gives at , and the time to it, the section class, the section factor, and each clause with its utilisation. The messages say:
- the used;
- the heating route: the section factor, and for protected steel , , and ;
- where it is reduced for thickness;
- the Class 4 route and its numbers;
- a held flange read as a restrained beam;
- (4.22) where it applies;
- read past the it is printed for, where a member's slenderness goes past it.
Not covered
- Stainless steel in fire, Annex C: refused. The EN 1993-1-4 module covers stainless steel at normal temperature only.
- Other sections: channels, angles, tees, circular tubes, cold-formed C and Z sections and outline sections are refused.
- The accidental combination (6.11b): not generated, so the forces are always .
- National annex choices in fire: and are the check's own settings, and the fixed critical temperatures or tables some annexes give are not offered.
- Torsion, the bimoment and shear along y are not read by this module.
- Non-uniform temperature over the section or along the member, other than through and ; parametric fires; the advanced calculation models of §4.3.
- Shorter fire buckling lengths for columns in braced frames, §4.2.3.2(5).
- Connections in fire, composite members, and the fire protection's own design.